BR-7M 3P 7kA Type 1+2 / B+C Surge Protective Device For TN-C

Get A Quote
Description

Product characteristics:

Specification BR-7M 150 3P BR-7M 275 3P BR-7M 320 3P
SPD classification according to EN61643-11 Type 1 + Type 2 Type 1 + Type 2 Type 1 + Type 2
SPD classification according to IEC61643-11 Class I + Class II Class I + Class II Class I + Class II
Max. continuous operating a.c. voltage Uc 150V(50/60Hz) 275V(50/60Hz) 320V(50/60Hz)
Lightning impulse current (10/350μs) Iimp 7kA 7kA 7kA
Nominal discharge current (8/20μs) In 25kA 25kA 25kA
Max. discharge current (8/20μs) Imax 60kA 60kA 60kA
Specific energy W/R 12.25kJ/Ω 12.25kJ/Ω 12.25kJ/Ω
Voltage protection level Up ≤0.8kV ≤1.3kV ≤1.5kV
Short-circuit current rating a.c. Isccr 25kA rms 25kA rms 25kA rms
Max. backup fuse 125A gG 125A gG 125A gG
Temporary overvoltage TOV-withstand UT(L-N) 175V/5sec. 335V/5sec. 350V/5sec.
Temporary overvoltage TOV-safe failure UT(L-N) 250V/120min. 440V/120min. 550V/120min.
Response time tA ≤25ns ≤25ns ≤25ns
Operating temperature range Tu -40℃-80℃ -40℃-80℃ -40℃-80℃
Cross-section area (Min.) 4mm² 4mm² 4mm²
Cross-section area (Max.) 35mm² 35mm² 35mm²
For mounting on 35mm Din rail
Enclosure material Thermoplastic UL94-V0
Degree of protection IP20 IP20 IP20
Order Code B17306 B17308 B17310
Order Code (With remote signaling) B17307 B17309 B17311

Features:

Equipped with a thermal disconnection.

BR-7M 3P is built with a plug-in module and fixed base, which allows an easy and fast maintenance.

DIN rail mounted surge protector is easy to install in any standardized distribution pane or control cabinets.

It is equipped with an internal thermal safety which will disconnect the unit from the AC network in case of the end of life. This disconnection will be indicated by the turn-on of the red mechanical indicator in the front.

Application:

BR-7M AC SPD is suitably used in the TN-C power supply system of AC 50/60HZ.

Suitable for system power protection, such as power distribution cabinet, switch cabinet, switch cabinet, AC distribution board, etc.

SPD to protect from direct and indirect lightning impulse and other transient over voltage.

Installation:

The protector is installed with standard 35mm track.

The protector is connected by 4 ~ 35mm copper wire.

No need to adjust after the protector is installed as required.

During operation, regularly check whether the module is red; replace the failed component in time.

WE ARE HERE TO SUPPORT YOU!

Further information or a personal consultation? Our products and know-how are there to provide solutions.