BR-40VG 1+1 Type 2 40kA Class II Surge Protector

Get A Quote
Description

Product characteristics:

Specification BR-40VG 150 1+1 BR-40VG 275 1+1 BR-40VG 320 1+1 BR-40VG 385 1+1 BR-40VG 440 1+1
SPD classification according to EN61643-11 Type 2 Type 2 Type 2 Type 2 Type 2
SPD classification according to IEC61643-11 Class II Class II Class II Class II Class II
Max. continuous operating a.c. voltage(L-N) Uc 150V 275V 320V 385V 440V
Max. continuous operating a.c. voltage(N-PE) Uc 255V 255V 255V 255V 255V
Nominal discharge current (8/20μs) In 20kA 20kA 20kA 20kA 20kA
Max. discharge current (8/20μs) Imax 40kA 40kA 40kA 40kA 40kA
Voltage protection level (L-N) Up ≤0.8kV ≤1.3kV ≤1.5kV ≤1.8kV ≤2.0kV
Voltage protection level 5kA (L-N) Up ≤0.6kV ≤1kV ≤1.2kV ≤1.4kV ≤1.6kV
Voltage protection level (N-PE) Up ≤1.5kV ≤1.5kV ≤1.5kV ≤1.5kV ≤1.5kV
Max. backup fuse 125A gG 125A gG 125A gG 125A gG 125A gG
Short-circuit withstand capacity Isccr 25kA 25kA 25kA 25kA 25kA
Temporary overvoltage TOV-withstand (L-N) UT 175V/5sec. 335V/5sec. 350V/5sec. 550V/5sec. 580V/5sec.
Temporary overvoltage TOV-safe failure(L-N) UT 250V/120min. 440V/120min. 550V/120min. 660V/120min. 770V/120min.
Temporary overvoltage TOV-withstand(N-PE) UT 1200V/200ms 1200V/200ms 1200V/200ms 1200V/200ms 1200V/200ms
Response time (L-N) tA ≤25ns ≤25ns ≤25ns ≤25ns ≤25ns
Response time (N-PE) tA ≤100ns ≤100ns ≤100ns ≤100ns ≤100ns
Operating temperature range Tu -40℃-80℃ -40℃-80℃ -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red green/red green/red
Cross-section area (Min.) 4mm² 4mm² 4mm² 4mm² 4mm²
Cross-section area (Max.) 35mm² 35mm² 35mm² 35mm² 35mm²
For mounting on 35mm Din rail
Enclosure material Thermoplastic   UL94-V0
Degree of protection IP20 IP20 IP20 IP20 IP20
Order Code B17508 B17520 B17532 B17544 B17556
Order Code (With remote signaling) B17509 B17521 B17533 B17545 B17557

Features:

These are suitable for second level of protection in supply distribution panels.

BR-40VG OEM Customized 1P+NPE Imax 40kA AC Power Supply SPD is designed according to IEC61643 standard.

BR-40VG series Surge Protection are designed to protect against lighting surge voltages.

End of Life Indicator (Red & Green).

Mechanically coded cartridges to avoid cartridge replacement errors.

There is an indicator on the cartridges to signal failure mode.

With good sealing, it is designed as module and 35mm DIN-Rail Mounting.

With or without floating remote indication contact

Temperature control circuit breaker and built-in over-current protective circuit, the modular SPD can release automatically to avoid fire danger when it breaks down.

Protection in small module width.

Faulty cartridges can be replaced without changing the entire SPD.

This industrial surge protector for AC helps prevent damage from VAC overvoltage that can be caused by lightning surge and other strong electrical power spikes.

Cartridges can be replaced with mains voltage ON.

This is installed in to each electrical switch boards and prevents the spread of surges in the electric systems, protecting the loads.

Application:

It can be installed in the low voltage power distribution cabinet/box of buildings, to protect all kinds of power equipment in the single phase power distribution system between LPZ1 and LPZ2.

Protection of terminal devices.

For example, low voltage general electricity Cabinet and/or distribution board of buildings, outdoor electricity cabinet/distribution box, any circumstance need to record the lightning leakage, power supply system: TT, TN.

Used for protection against electrical transients.

WE ARE HERE TO SUPPORT YOU!

Further information or a personal consultation? Our products and know-how are there to provide solutions.

RELATED PRODUCTS
RELATED NEWS
YOU MAY ALSO WANT TO SEE
GET SURGE PROTECTION
SOLUTIONSTODAY!
icon
icon
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.