BR-60 4P Type 2 60kA Surge Protective Device For TNS

Get A Quote
Description

Product characteristics:

Specification BR-60 150 4P BR-60 275 4P BR-60 320 4P BR-60 385 4P
SPD classification according to EN61643-11 Type 2 Type 2 Type 2 Type 2
SPD classification according to IEC61643-11 Class II Class II Class II Class II
Max. continuous operating a.c. voltage Uc 150V 275V 320V 385V
Nominal discharge current (8/20μs) In 30kA 30kA 30kA 30kA
Max. discharge current (8/20μs) Imax 60kA 60kA 60kA 60kA
Voltage protection level Up ≤1.0kV ≤1.6kV ≤1.8kV ≤2.2kV
Voltage protection level 5kA Up ≤0.5kV ≤0.6kV ≤1.0kV ≤1.2kV
Max. backup fuse 160A gG 160A gG 160A gG 160A gG
Short-circuit withstand capacity Isccr 25kA 25kA 25kA 25kA
Temporary overvoltage TOV-withstand UT 175V/5sec. 335V/5sec. 350V/5sec. 550V/5sec.
Temporary overvoltage TOV-safe failure UT 250V/120min. 440V/120min. 550V/120min. 660V/120min.
Response time tA ≤25ns ≤25ns ≤25ns ≤25ns
Operating temperature range Tu -40℃-80℃ -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red green/red
Cross-section area (Min.) 4mm² 4mm² 4mm² 4mm²
Cross-section area (Max.) 35mm² 35mm² 35mm² 35mm²
For mounting on 35mm Din rail
Enclosure material Thermoplastic   UL94-V0
Degree of protection IP20 IP20 IP20 IP20
Order Code B18761 B18763 B18765 B18767
Order Code (With remote signaling) B18762 B18764 B18766 B18768

Features:

BR-60 4P surge protective device (hereinafter referred to as SPD) are suitable for AC 50/60Hz, TN-S power supply system.

Indicating window: Green: normal function; Red: functionless, immediate replacement required.

It protect to indirect and direct lightning effect or other transient over voltage.

This Class C surge protective device consisting of a base part and MOV plug-in protection modules.

SPD design according with GB18802.1/IEC61643-11 standard.

Application:

BR-60 series surge protective devices suitable for C grade surge protection, which protects the electrical network not shocked by the thunder.

Suitable for lightning and surge protection in AC 50/60Hz.

Used in AC power line of house, bank, telecom tower and so on.

WE ARE HERE TO SUPPORT YOU!

Further information or a personal consultation? Our products and know-how are there to provide solutions.