BR-40DP 4P 40kA Compact Surge Protective Device For TNS

Get A Quote
Description

Product characteristics:

Specification BR275-40DP 4P BR320-40DP 4P
SPD classification according to EN61643-11 Type 2 + Type 3 Type 2 + Type 3
SPD classification according to IEC61643-11 Class II + Class III Class II + Class III
Max. continuous operating a.c. voltage Uc 275V 320V
Nominal discharge current (8/20μs) In 20kA 20kA
Max. discharge current (8/20μs) Imax 40kA 40kA
Combined impulse Uoc 10kV 10kV
Voltage protection level Up ≤1.3kV ≤1.5kV
Response time tA ≤25ns ≤25ns
Operating temperature range Tu -40℃-80℃ -40℃-80℃
Operating state / fault indication green / red green / red
Cross-section area (Min.) 2.5mm² 2.5mm²
Cross-section area (Max.) 16mm² 16mm²
For mounting on 35mm Din rail 35mm Din rail
Enclosure material Thermoplastic UL94-V0
Degree of protection IP20 IP20
Order code B18220 B17250
Order code (with remote signal) B18221 B17251

Features:

Type 2 + Type 3 Surge Protector.

Discharge currents : In : 20 kA / Imax : 40 kA.

DIN rail compatible.

Remote Signalling in option.

IEC 61643-11 and EN 61643-11 compliance.

Visible fault indication:Green on: Normal; Green off: Fault.

BR-40DP series is combined Type 2+3 / Class II+III devices for discharging voltage surges while providing a very fine voltage protection level.

Application:

For protection of power supply systems.

For the protection of low voltage distribution systems against transient overvoltage caused by indirect lightning stroke and switching operations.

For using in the lightning protection zones concept at boundary 2-3.

Applied to power supply protection of equipment system in areas with high lightning risk.

Installation:

Suitable as the final stage of protection in panels with Type 2 protection devices installed upstream.

These SPDs should be installed as close as possible to the equipment being protected.

Installed at a minimum conductor length of 10 meters (30 feet) from the electrical service panel to the point of utilization, for example cord connected, direct plug-in, receptacle type SPDs installed at the utilization equipment being protected. The distance (10 meters) is exclusive of the conductors provided with or used to attach SPDs.

WE ARE HERE TO SUPPORT YOU!

Further information or a personal consultation? Our products and know-how are there to provide solutions.

RELATED PRODUCTS
RELATED NEWS
YOU MAY ALSO WANT TO SEE
GET SURGE PROTECTION
SOLUTIONSTODAY!
icon
icon
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.