BRBE-4L SPDs For Dataline

Get A Quote
Description

Product characteristics:

Specification BRBE-4L-6 BRBE-4L-12 BRBE-4L-24 BRBE-4L-48 BRBE-4L-60 BRBE-4L-180
SPD class TYPE2 P1 TYPE2 P1 TYPE2 P1 TYPE2 P1 TYPE2 P1 TYPE2 P1
Norminal voltage Un 5V 12V 24V 48V 60V 180V
Max. continuous operating d.c. voltage Uc 6V 15V 33V 54V 70V 180V
Max. continuous operating a.c. voltage Uc 4.2V 10.6V 23.3V 38.1V 49.5V 127V
Nominal current at 45℃ IL 1A 0.75A 0.75A 0.75A 1A 1A
C2 Total Norminal discharge current (8/20μs) In 20kA 20kA 20kA 20kA 20kA 20kA
C2 Nominal discharge current (8/20μs) per line In 10kA 10kA 10kA 10kA 10kA 10kA
Voltage protection level line-line for In C2 Up ≤40V ≤55V ≤105V ≤170V ≤220V ≤550V
Voltage protection level line-PG for In C2 Up ≤60V ≤60V ≤85V ≤115V ≤155V ≤300V
Voltage protection level line-line at 1 kV/μs C3 Up ≤18V ≤38V ≤90V ≤140V ≤180V ≤500V
Voltage protection level line-PG at 1 kV/μs C3 Up ≤9V ≤19V ≤45V ≤70V ≤90V ≤250V
Series impedance per line 1 Ohm 1.8 Ohm 1.8 Ohm 1.8 Ohm 1 Ohm 1 Ohm
Cut-off frequency line-PG fG 1.0 MHz 2.7 MHz 6.8 MHz 8.7 MHz 9.0 MHz 25.0 MHz
Capacitance line-line C ≤2.7nF ≤1.0nF ≤0.5nF ≤0.35nF ≤250pF ≤120pF
capacitance line-PG C ≤5.4nF ≤2.0nF ≤1.0nF ≤0.7nF ≤500pF ≤240pF
Operating temperature range Tu -40℃…+80℃
Enclosure material Polyamide PA 6.6
Degree of protection (plugged-in) IP 20 IP 20 IP 20 IP 20 IP 20 IP 20
Order Code D9116 D9117 D9118 D9119 D9120 D9121

Features:

Version: Plug-in.

Nominal voltage: 5V, 12V, 24V, 48V, 60V, 180V.

Nominal current at 45℃: 1A / 0.75A.

Total nominal discharge current (8/20us) 20kA.

Frequency: 1.0 MHz / 2.8 MHz / 7.8 MHz / 8.7 MHz / 11.0 MHz / 25.0 MHz.

SPDs for Din rail mounting to enable easy installation.

Degree of protection: IP20.

The product can provide protection for four lines for general information.

Installation:

The ground point of the surge protector and of the protected equipment must be bonded.

The protection is installed at the service entrance of the installation to divert impulse current as soon as possible.

The earth resistance must adhere to the local electrical code.

Protected and unprotected cables must be kept well apart to limit coupling.

WE ARE HERE TO SUPPORT YOU!

Further information or a personal consultation? Our products and know-how are there to provide solutions.

RELATED PRODUCTS
RELATED NEWS
YOU MAY ALSO WANT TO SEE
GET SURGE PROTECTION
SOLUTIONSTODAY!
icon
icon
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.