BR-25VG 1+1 25kA Type 1 Surge Protector

Get A Quote
Description

Product characteristics:

Specification BR-25VG 320 1+1 BR-25VG 440 1+1 BR-25VG 690 1+1
SPD classification according to EN61643-11 Type 1 + Type 2 +Type 3
SPD classification according to IEC61643-11 Class I + Class II + Class III
Nominal operating voltage Un 250V/440V(50/60Hz) 250V/440V(50/60Hz) 400V/690V(50/60Hz)
Max. continuous operating a.c. voltage Uc(L-N/N-PE) 320V/255V(50/60Hz) 440V/255V(50/60Hz) 690V/255V(50/60Hz)
Lightning impulse current (10/350μs) Iimp(L-N/N-PE) 25kA/50kA 25kA/50kA 25kA/50kA
Total discharge current (10/350μs) Itotal 50kA 50kA 50kA
Nominal discharge current (8/20μs) In(L-N/N-PE) 30kA/50kA 30kA/50kA 30kA/50kA
Max. discharge current (8/20μs) Imax(L-N/N-PE) 70kA/100kA 70kA/100kA 70kA/100kA
Quantity of electric charge Q 12.5As/25As 12.5As/25As 12.5As/25As
Specific energy W/R 156kJ/Ω, 625kJ/Ω 156kJ/Ω, 625kJ/Ω 156kJ/Ω, 625kJ/Ω
Voltage protection level Up(L-N/N-PE) ≤1.5kV/≤1.5kV ≤1.8kV/≤1.5kV ≤2.5kV/≤1.5kV
Short-circuit current rating a.c. Isccr(L-N/N-PE) 25kA rms/100A rms 25kA rms/100A rms 25kA rms/100A rms
Max. backup fuse 200A gG 200A gG 200A gG
Temporary overvoltage TOV-withstand UT(L-N) 350V/5sec. 580V/5sec. 880V/5sec.
Temporary overvoltage TOV-safe failure UT(L-N) 550V/120min. 770V/120min. 1100V/120min.
Temporary overvoltage TOV-withstand UT(N-PE) 1200V/200ms 1200V/200ms 1200V/200ms
Leakage current Ipe 0mA 0mA 0mA
Response time tA(L-N/N-PE) ≤25ns/≤100ns ≤25ns/≤100ns ≤25ns/≤100ns
Operating temperature range Tu -40℃-80℃ -40℃-80℃ -40℃-80℃
Cross-section area (Min.) 4mm² 4mm² 4mm²
Cross-section area (Max.) 35mm² 35mm² 35mm²
For mounting on 35mm Din rail
Enclosure material Thermoplastic UL94-V0
Degree of protection IP20 IP20 IP20
Order Code B17271 B17283 B17295
Order Code (With remote signaling) B17272 B17284 B17296

Features:

Response time: ≤25ns/≤100ns

Powerful components, suitable for all kinds of common power systems.

Nominal discharge current (8/20us): 30kA

The unit is designed to be used between Zone O and Zone 1 (according to IEC62305-4 definition of Lightning Protection Area).

Temperature range: -40℃—80℃

Simple standard rail mounting.

Class I+II+III / Type 1+2+3 surge protection.

Application:

• The Type 1 surge protector is usually installed at the junction of LPZ0B and LPZ1

• It can be installed in the low voltage power distribution cabinet/box of building.

• It is suitable for distribution cabinets and distribution boxes with outdoor access lines in buildings.

Installation:

• Power must be cut off before installation. Live operation is prohibited.

• It is recommended that a fuse or circuit breaker be connected in series at the front end of the surge protection.

• SPD is installed in parallel at the power supply inlet end of the building distribution box or the equipment room. The product is installed in the guide rail type. If conditions permit, the Kevin connection mode can be adopted.

• During installation, connect the device according to the installation diagram, where L is the phase line,N is the neutral line, and PE is the ground line. Do not misconnect the device. After the installation is complete, turn on the automatic circuit breaker and check whether the working status is normal.

• When the SPD is in use, check the status of the fault display window regularly. If the fault display window is red or the remote terminal outputs an alarm signal, it indicates that the SPD is faulty and should be repaired or replaced in time.

• Suitable for indoor operation, such as installed in the outdoor, must be equipped with waterproof shell.

WE ARE HERE TO SUPPORT YOU!

Further information or a personal consultation? Our products and know-how are there to provide solutions.

RELATED PRODUCTS
RELATED NEWS
YOU MAY ALSO WANT TO SEE
GET SURGE PROTECTION
SOLUTIONSTODAY!
icon
icon
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.