Product characteristics:
Specification | BR-12.5M 150 4P | BR-12.5M 275 4P | BR-12.5M 320 4P | |
SPD classification according to EN61643-11 | Type 1 + Type 2 | Type 1 + Type 2 | Type 1 + Type 2 | |
SPD classification according to IEC61643-11 | Class I + Class II | Class I + Class II | Class I + Class II | |
Max. continuous operating a.c. voltage | Uc | 150V(50/60Hz) | 275V(50/60Hz) | 320V(50/60Hz) |
Lightning impulse current (10/350μs) | Iimp | 12.5kA | 12.5kA | 12.5kA |
Nominal discharge current (8/20μs) | In | 25kA | 25kA | 25kA |
Max. discharge current (8/20μs) | Imax | 60kA | 60kA | 60kA |
Specific energy | W/R | 39kJ/Ω | 39kJ/Ω | 39kJ/Ω |
Voltage protection level | Up | ≤0.8kV | ≤1.3kV | ≤1.5kV |
Short-circuit current rating a.c. | Isccr | 25kA rms | 25kA rms | 25kA rms |
Max. backup fuse | 125A gG | 125A gG | 125A gG | |
Temporary overvoltage TOV-withstand | UT(L-N) | 175V/5sec. | 335V/5sec. | 350V/5sec. |
Temporary overvoltage TOV-safe failure | UT(L-N) | 250V/120min. | 440V/120min. | 550V/120min. |
Response time | tA | ≤25ns | ≤25ns | ≤25ns |
Operating temperature range | Tu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ |
Cross-section area (Min.) | 4mm² | 4mm² | 4mm² | |
Cross-section area (Max.) | 35mm² | 35mm² | 35mm² | |
For mounting on | 35mm Din rail | |||
Enclosure material | Thermoplastic UL94-V0 | |||
Degree of protection | IP20 | IP20 | IP20 | |
Order Code | B18411 | B18413 | B18415 | |
Order Code (With remote signaling) | B18412 | B18414 | B18416 |
Features:
Type 1+2, T1+T2, B+C, I+II, Iimp 12.5 kA is developed as the best solution available to protect service entrance at industrial sites.
It is designed to meet all your needs for any low voltage installation.
It is easy to install in any standardized distribution pane or control cabinets.
It has a 10/350 μs current waveform.
It is equipped with a thermal disconnection device and provide real-time fault indicators thus allowing complete operational safety.
Use the pluggable module set up, the maintenance is simple
Din rail mountable (35 mm)
It has the characteristics of low residual pressure, sensitive reaction, stable performance, reliable work and so on.
With remote signaling contact for control device.
It’s designed according to GB18802.1 IEC61643-11
Fault indication via red mark in the inspection window.
Application:
To prevent power supply equipment from being damaged by surge and lightning.
Use on buildings in applications where there is an external lightning protection system installed, usually installed at the service entrance.
Widely used in the transformer low-voltage side as the first protection of the power supply.
Installation:
Installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage.
Install in the main distribution cabinet/box of the low-voltage cabinet and the incoming line cabinet.
Recommended for main distribution boards.
During installation, please connect according to the installation schematic diagram, where L1, L2 and L3 are phase lines, N is the zero line and PE is the ground line.
Grounding should conform to the requirements of the specification of lightning protection.
Further information or a personal consultation? Our products and know-how are there to provide solutions.