...

BR-12.5M 2P 12.5kA Type 1+2 Surge Protective Device For TNS

Get A Quote
Description

Product characteristics:

Specification BR-12.5M 150 2P BR-12.5M 275 2P BR-12.5M 320 2P
SPD classification according to EN61643-11 Type 1 + Type 2 Type 1 + Type 2 Type 1 + Type 2
SPD classification according to IEC61643-11 Class I + Class II Class I + Class II Class I + Class II
Max. continuous operating a.c. voltage Uc 150V(50/60Hz) 275V(50/60Hz) 320V(50/60Hz)
Lightning impulse current (10/350μs) Iimp 12.5kA 12.5kA 12.5kA
Nominal discharge current (8/20μs) In 25kA 25kA 25kA
Max. discharge current (8/20μs) Imax 60kA 60kA 60kA
Specific energy W/R 39kJ/Ω 39kJ/Ω 39kJ/Ω
Voltage protection level Up ≤0.8kV ≤1.3kV ≤1.5kV
Short-circuit current rating a.c. Isccr 25kA rms 25kA rms 25kA rms
Max. backup fuse 125A gG 125A gG 125A gG
Temporary overvoltage TOV-withstand UT(L-N) 175V/5sec. 335V/5sec. 350V/5sec.
Temporary overvoltage TOV-safe failure UT(L-N) 250V/120min. 440V/120min. 550V/120min.
Response time tA ≤25ns ≤25ns ≤25ns
Operating temperature range Tu -40℃-80℃ -40℃-80℃ -40℃-80℃
Cross-section area (Min.) 4mm² 4mm² 4mm²
Cross-section area (Max.) 35mm² 35mm² 35mm²
For mounting on 35mm Din rail
Enclosure material Thermoplastic UL94-V0
Degree of protection IP20 IP20 IP20
Order Code B18211 B18213 B18215
Order Code (With remote signaling) B18212 B18214 B18216

Features:

Type 1+2.

High discharge capacity in a certain small size.

High follow current extinction and limitation due to no follow current technology.

Reliable safety due to double integrated disconnections with double protections.

Failure indication window, remote alarm terminal optional.

Plug design, easy maintenance.

High security performance.

Green light in notice window indicates normal; red indicates broken, replacement notice, which is clear and easy distinguished.

Indoor fixed installation, voltage limited type.

Small volume, pluggable.

Application:

To prevent power supply equipment from being damaged by surge and lightning.

Use on buildings in applications where there is an external lightning protection system installed, usually installed at the service entrance.

Widely used in the transformer low-voltage side as the first protection of the power supply.

Installation:

Installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage.

Install in the main distribution cabinet/box of the low-voltage cabinet and the incoming line cabinet.

Recommended for main distribution boards.

During installation, please connect according to the installation schematic diagram, where L1, L2 and L3 are phase lines, N is the zero line and PE is the ground line.

Grounding should conform to the requirements of the specification of lightning protection.

WE ARE HERE TO SUPPORT YOU!

Further information or a personal consultation? Our products and know-how are there to provide solutions.

RELATED PRODUCTS
RELATED NEWS
YOU MAY ALSO WANT TO SEE
GET SURGE PROTECTION
SOLUTIONSTODAY!
icon
icon
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.