Product characteristics:

Specification BR230-30 BR230-75 BR230-150 BR230-275
SPD classification according to EN61643-11 Type 3 Type 3 Type 3 Type 3
SPD classification according to IEC61643-11 Class III Class III Class III Class III
Nominal a.c. voltage Un 24V 60V 120V 230V
Max. continuous operating a.c. voltage Uc 30V 75V 150V 275V
Max. continuous operating d.c. voltage Uc 38V 100V 180V 300V
Nominal discharge current (8/20μs) In 5kA 5kA 5kA 5kA
Nominal load current a.c. IL 25A 25A 25A 25A
Combined impulse Uoc 10kV 10kV 10kV 10kV
Voltage protection level Up ≤630V ≤730V ≤800V ≤1500V
Response time (L-N / L/N-PE) tA ≤25ns/≤100ns ≤25ns/≤100ns ≤25ns/≤100ns ≤25ns/≤100ns
Operating temperature range Tu -40℃-80℃ -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state / fault indication green / red green / red green / red green / red
Cross-section area (Min.) 1mm² 1mm² 1mm² 1mm²
Cross-section area (Max.) 4mm² solid/2.5mm² flexible
For mounting on 35mm Din rail 35mm Din rail 35mm Din rail 35mm Din rail
Enclosure material Thermoplastic UL94-V0
Degree of protection IP20 IP20 IP20 IP20
Order code B18237 B18235 B18359 B18231
Order code (with remote signal) B18238 B18236 B18234 B18232

Features:

BR-230 series surge protector is for protecting low-voltage consumer’s installations against indirect lightning discharges.

Module design, convenient installation.

is to be installed in LEPM zone: LPZ2 – LPZ3.

Nominal Discharge Current (8/20us): 5kA.

It consists of a high performance varistor with thermal disconnection tripping device.

Signal indication device, green (normal), red (abnormal).

New technology, highly energy.

Production Standard: IEC61643-11.

Application:

Used for electrical networks, electrical installations, and electronic equipment.