Product characteristics:
Specification | BR-40VG 150 1P | BR-40VG 275 1P | BR-40VG 320 1P | BR-40VG 385 1P | BR-40VG 440 1P | |
SPD classification according to EN61643-11 | Type 2 | Type 2 | Type 2 | Type 2 | Type 2 | |
SPD classification according to IEC61643-11 | Class II | Class II | Class II | Class II | Class II | |
Max. continuous operating a.c. voltage | Uc | 150V | 275V | 320V | 385V | 440V |
Nominal discharge current (8/20μs) | In | 20kA | 20kA | 20kA | 20kA | 20kA |
Max. discharge current (8/20μs) | Imax | 40kA | 40kA | 40kA | 40kA | 40kA |
Voltage protection level | Up | ≤0.8kV | ≤1.3kV | ≤1.5kV | ≤1.8kV | ≤2.0kV |
Voltage protection level 5kA | Up | ≤0.6kV | ≤1kV | ≤1.2kV | ≤1.4kV | ≤1.6kV |
Max. backup fuse | 125A gG | 125A gG | 125A gG | 125A gG | 125A gG | |
Short-circuit withstand capacity | Isccr | 25kA | 25kA | 25kA | 25kA | 25kA |
Temporary overvoltage TOV-withstand | UT | 175V/5sec. | 335V/5sec. | 350V/5sec. | 550V/5sec. | 580V/5sec. |
Temporary overvoltage TOV-safe failure | UT | 250V/120min. | 440V/120min. | 550V/120min. | 660V/120min. | 770V/120min. |
Response time | tA | ≤25ns | ≤25ns | ≤25ns | ≤25ns | ≤25ns |
Operating temperature range | Tu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ |
Operating state/fault indication | green/red | green/red | green/red | green/red | green/red | |
Cross-section area (Min.) | 4mm² | 4mm² | 4mm² | 4mm² | 4mm² | |
Cross-section area (Max.) | 35mm² | 35mm² | 35mm² | 35mm² | 35mm² | |
For mounting on | 35mm Din rail | |||||
Enclosure material | Thermoplastic UL94-V0 | |||||
Degree of protection | IP20 | IP20 | IP20 | IP20 | IP20 | |
Order Code | B17500 | B17512 | B17524 | B17536 | B17548 | |
Order Code (With remote signaling) | B17501 | B17513 | B17525 | B17537 | B17549 |
Features:
Class II / Type 2 lightning protective device.
In: 20kA.
For using in the lightning protection zones concept at boundary 1-2.
Module design, convenient installation
Low residual voltage and quick response.
Time of response ˂ 25ns
With remote signaling contact for control device.
Protecting low-voltage consumers’ installations against indirect lightning discharges.
Fault indication via red mark in the inspection window.
Power Source : Electric
Plug-in module/base design facilitate replacement of a failed module without the need to remove system wiring etc.
Application:
Protection of an electrical installation and all electrical and electronic devices connected this installation against destructive overvoltage surges.
Surge arresters cover the protection of home appliances, commercial building equipment, and industrial equipment.
The devices are especially designed to provide complete and effective protection against surges, protecting equipment and property connected to the low voltage network.