BR-7M 1P 7kA Type 1+2 / B+C Surge Protective Device

Get A Quote
Description

Product characteristics:

Specification BR-7M 150 1P BR-7M 275 1P BR-7M 320 1P
SPD classification according to EN61643-11 Type 1 + Type 2 Type 1 + Type 2 Type 1 + Type 2
SPD classification according to IEC61643-11 Class I + Class II Class I + Class II Class I + Class II
Max. continuous operating a.c. voltage Uc 150V(50/60Hz) 275V(50/60Hz) 320V(50/60Hz)
Lightning impulse current (10/350μs) Iimp 7kA 7kA 7kA
Nominal discharge current (8/20μs) In 25kA 25kA 25kA
Max. discharge current (8/20μs) Imax 60kA 60kA 60kA
Specific energy W/R 12.25kJ/Ω 12.25kJ/Ω 12.25kJ/Ω
Voltage protection level Up ≤0.8kV ≤1.3kV ≤1.5kV
Short-circuit current rating a.c. Isccr 25kA rms 25kA rms 25kA rms
Max. backup fuse 125A gG 125A gG 125A gG
Temporary overvoltage TOV-withstand UT(L-N) 175V/5sec. 335V/5sec. 350V/5sec.
Temporary overvoltage TOV-safe failure UT(L-N) 250V/120min. 440V/120min. 550V/120min.
Response time tA ≤25ns ≤25ns ≤25ns
Operating temperature range Tu -40℃-80℃ -40℃-80℃ -40℃-80℃
Cross-section area (Min.) 4mm² 4mm² 4mm²
Cross-section area (Max.) 35mm² 35mm² 35mm²
For mounting on 35mm Din rail
Enclosure material Thermoplastic UL94-V0
Degree of protection IP20 IP20 IP20
Order Code B17318 B17320 B17322
Order Code (With remote signaling) B17319 B17321 B17323

Features:

The technical performance of the products meets the standard technical equipment of GB18802.1 and IEC61643-11.

It adopts 35mm standard rail.

This model designed in modular with excellent airtight property.

It is with 35mm din rail, which make it easy for installation.

Application:

Installation at LPZ 0 -1 or higher, protecting low voltage equipment.

Applied in PSD Class I+II (Class B+C).

Connected to AC low-voltage power systems for protection of equipment from transient over-voltage caused by the inducted lightning stroke or internal power systems.

Installation:

The protector is installed with standard 35mm track.

The protector is connected by 4 ~ 35mm copper wire.

No need to adjust after the protector is installed as required.

During operation, regularly check whether the module is red; replace the failed component in time.