Product characteristics:
Specification | BR-ME-12 | BR-ME-24 | BR-ME-48 | BR-ME-110 | |
Test standards | IEC 61643-21 | ||||
SPD class | TYPE2 P1 | TYPE2 P1 | TYPE2 P1 | TYPE2 P1 | |
Norminal voltage | Un | 12V | 24V | 48V | 110V |
Max. continuous operating d.c. voltage | Uc | 14V | 33V | 55V | 170V |
Max. continuous operating a.c. voltage | Uc | 9.5V | 23V | 38.5V | 120V |
Nominal current at 45℃ | IL | 0.5A | 0.5A | 0.5A | 0.5A |
C2 Total Norminal discharge current (8/20μs) | In | 10kA | 10kA | 10kA | 10kA |
C2 Nominal discharge current (8/20μs) per line | In | 5kA | 5kA | 5kA | 5kA |
Voltage protection level line-line for In C2 | Up | ≤55V | ≤110V | ≤175V | ≤500V |
Voltage protection level line-PG for In C2 | Up | ≤40V | ≤65V | ≤100V | ≤270V |
Voltage protection level line-line at 1 kV/μs C3 | Up | ≤36V | ≤90V | ≤160V | ≤460V |
Voltage protection level line-PG at 1 kV/μs C3 | Up | ≤19V | ≤45V | ≤80V | ≤230V |
Series impedance per line | 1.8 Ohm | 1.8 Ohm | 1.8 Ohm | 1.8 Ohm | |
Cut-off frequency line-PG | fG | 2.5 MHz | 6 MHz | 10 MHz | 16 MHz |
Capacitance line-line | C | ≤1.2nF | ≤0.5nF | ≤0.3nF | ≤0.2nF |
capacitance line-PG | C | ≤2.4nF | ≤1.0nF | ≤0.6nF | ≤0.4nF |
Operating temperature range | Tu | -40℃-80℃ | |||
Cross section of cable | 0.08-2.5mm2 | 0.08-2.5mm2 | 0.08-2.5mm2 | 0.08-2.5mm2 | |
Enclosure material | polyamide PA 6.6 | ||||
Degree of protection (plugged-in) | IP20 | IP20 | IP20 | IP20 | |
Order Code | D9131 | D9132 | D9133 | D9134 |
Features:
Total nominal discharge current (8/20us) up to 10kA.
Test Standards for communication line surge protectors comply with IEC 61643-21: Tests of Surge Protectors for Communication Lines.
Data surge protection provides a complete solution to avoid damage, downtime and power outages.
Application:
Provide transient protection for the device against surge.
Protects equipment from data line surges.
Protect against lightning strikes, power surges, and other types of voltage disturbances.