Product characteristics:
Specification | BRPV2-600 | |
SPD classification according to EN61643-31 / IEC61643-31 | Type 2 / Class II | |
Max. continuous operating d.c. voltage | Ucpv | 600V |
Nominal discharge current (8/20μs) | In | 20kA |
Max. discharge current (8/20μs) | Imax | 40kA |
Voltage protection level [(DC+/DC-)→PE] | Up | ≤2.2kV |
Response time | tA | ≤25ns |
Operating temperature range | Tu | -40℃-80℃ |
Operating state / fault indication | green / red | |
Cross-section area (Min.) | 4mm² | |
Cross-section area (Max.) | 35mm² | |
For mounting on | 35mm Din rail | |
Enclosure material | Thermoplastic UL94-V0 | |
Degree of protection | IP20 | |
Order code | B18013 | |
Order code (with remote signal) | B18015 |
Features:
2 modular.
Rated voltage 600V DC.
Imax: 40kA.
Status indication.
With remote indication contact.
For DIN rail mounting.
Conform to IEC61643-31 and EN61643-31.
Application:
For Photovoltaic applications to prevent the risks linked to lightning.
Applied to electrical systems to provide a discharge path to earth to save those systems’ components from being exposed to the high-voltage transients caused by the direct or indirect effects of lightning or power system anomalies.