Product characteristics:
Specification | BRRL-P-VG | BRRL-P-NG | BRRL-P-TT | |
SPD classification according to EN61643-11 | Type 2 + Type 3 | Type 2 + Type 3 | Type 2 + Type 3 | |
SPD classification according to IEC61643-11 | Class II + Class III | Class II + Class III | Class II + Class III | |
Nominal a.c. voltage | Un | 230V | 230V | 230V |
Max. continuous operating a.c. voltage | Uc | 275V | 275V | 275V |
Frequency | 50-60Hz | 50-60Hz | 50-60Hz | |
Norminal discharge current (8/20μs) | In | 5kA | 5kA | 5kA |
Maximum discharge current (8/20μs) | Imax | 20kA | 20kA | 20kA |
Voltage protection level | Up | ≤1.3kV | ≤1.3kV | ≤1.3kV |
Combined impulse | Uoc | 10KV | 10KV | 10KV |
Response time | tA | ≤100ns | ≤100ns | ≤100ns |
Operating temperature range | Tu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ |
Operating state / fault indication | green light on: OK; green light off: replace | |||
Enclosure material | Thermoplastic UL94-V0 | |||
Degree of protection | IP65 | IP65 | IP65 | |
Order code | B6011 | B6012 | B6013 |
Features:
Surge protective devices connected between the power supply and the LED light for protection of LED light from surge and transient over-voltage caused by the inducted lightning stroke or by internal power systems.
Belongs to Class II+III SPD
Compact size
The max. discharge current is 20kA/line.
Customized products are also available.
LED status indicator
Standards: EN 61643-11 (Surge Protection Devices).
Application:
Protect vulnerable equipment against the adverse effects produced by voltage spikes.
Protect LED lighting and the LED driver.
Suitable for LED Lighting, Roadway lighting, Traffic lighting, Digital signage, Wash wall lighting, Parking garage/lot lighting, Flood lighting, Tunnel lighting, Street lighting etc.
The surge protection device is also suitable for the protection of very sensitive components.
Notice:
After installing, the cable shall not be placed under direct sunlight to avoid expediting aging of the insulating