BR-12.5M 1P 12.5kA Type 1+2 Surge Protective Device

Get A Quote
Description

Product characteristics:

Specification BR-12.5M 150 1P BR-12.5M 275 1P BR-12.5M 320 1P
SPD classification according to EN61643-11 Type 1 + Type 2 Type 1 + Type 2 Type 1 + Type 2
SPD classification according to IEC61643-11 Class I + Class II Class I + Class II Class I + Class II
Max. continuous operating a.c. voltage Uc 150V(50/60Hz) 275V(50/60Hz) 320V(50/60Hz)
Lightning impulse current (10/350μs) Iimp 12.5kA 12.5kA 12.5kA
Nominal discharge current (8/20μs) In 25kA 25kA 25kA
Max. discharge current (8/20μs) Imax 60kA 60kA 60kA
Specific energy W/R 39kJ/Ω 39kJ/Ω 39kJ/Ω
Voltage protection level Up ≤0.8kV ≤1.3kV ≤1.5kV
Short-circuit current rating a.c. Isccr 25kA rms 25kA rms 25kA rms
Max. backup fuse 125A gG 125A gG 125A gG
Temporary overvoltage TOV-withstand UT(L-N) 175V/5sec. 335V/5sec. 350V/5sec.
Temporary overvoltage TOV-safe failure UT(L-N) 250V/120min. 440V/120min. 550V/120min.
Response time tA ≤25ns ≤25ns ≤25ns
Operating temperature range Tu -40℃-80℃ -40℃-80℃ -40℃-80℃
Cross-section area (Min.) 4mm² 4mm² 4mm²
Cross-section area (Max.) 35mm² 35mm² 35mm²
For mounting on 35mm Din rail
Enclosure material Thermoplastic UL94-V0
Degree of protection IP20 IP20 IP20
Order Code B18171 B18173 B18175
Order Code (With remote signaling) B18172 B18174 B18176

Features:

Surge arrestor.

Meet the type 1+2 requirement class according to IEC 61643-11.

High arresting capacity up to 12.5 kA (10/350μs).

Visual status display.

The use of high-performance varistors permits a rapid response time and a low protection level, without any line follow current.

Available with optional remote signaling.

Simple standard Din rail mounting.

Labeled connections.

Uc: 150v, 275v, 320v.

Based on high energy Metal Oxide Varistors.

Versions with 1P, 1+NPE, 2P, 3P, 3+NPE and 4P.

Exclusive devices for TN-S, TN-C and TT systems.

Reversible chassis to allow cable entry from above or below.

Indoor fixed installation, voltage limited type.

Module design.

Large lightning current discharge capacity.

Easy to maintain.

When the SPD works normally, the visible window displays green, and when it fails, it displays red.

Time of response<25ns.

Could supply different working voltage level and lightning discharge current, also could customized according to different requirement.

Application:

Usable in systems with lightning protection class 1+2.

Installation:

Please connect according to the installation diagram; the connecting wires must meet the requirements.

When the failure display window of the module indicates red, it means that the lightning protection device has failed, and new products should be replaced in time.

WE ARE HERE TO SUPPORT YOU!

Further information or a personal consultation? Our products and know-how are there to provide solutions.

RELATED PRODUCTS
RELATED NEWS
YOU MAY ALSO WANT TO SEE
GET SURGE PROTECTION
SOLUTIONSTODAY!
icon
icon