BR-40DP 3+1 40kA Compact Surge Protective Device For TT And TNS

Get A Quote
Description

Product characteristics:

Specification BR275-40DP 3+1 BR320-40DP 3+1
SPD classification according to EN61643-11 Type 2 + Type 3 Type 2 + Type 3
SPD classification according to IEC61643-11 Class II + Class III Class II + Class III
Max. continuous operating a.c. voltage Uc(L-N/N-PE) 275V/255V 320V/255V
Nominal discharge current (8/20μs) In 20kA 20kA
Max. discharge current (8/20μs) Imax 40kA 40kA
Combined impulse Uoc 10kV 10kV
Voltage protection level Up(L-N/N-PE) ≤1.3kV/≤1.5kV ≤1.5kV/≤1.5kV
Response time tA ≤25ns ≤25ns
Operating temperature range Tu -40℃-80℃ -40℃-80℃
Operating state / fault indication green / red green / red
Cross-section area (Min.) 2.5mm² 2.5mm²
Cross-section area (Max.) 16mm² 16mm²
For mounting on 35mm Din rail 35mm Din rail
Enclosure material Thermoplastic UL94-V0
Degree of protection IP20 IP20
Order code B18243 B17254
Order code (with remote signal) B18244 B17255

Features:

Type 2 + Type 3 Surge Protector.

Uc 275V/320V.

This three phase SPD din-rail for lightning protection and other spikes in electrical power has a maximum amperage of 40 kA.

Response time: ≤25ns.

Pole number: 2P, 4P, 1P+N, 3P+N.

UL 94 V-0 Thermoplastic Housing.

DIN rail compatible.

Remote Signaling in option.

Degree of protection: IP20.

Conforming fully to international IEC 61643-11 and EN 61643-11 standards.

It can provide type 3 protection for equipment which installed within 5 meters from these devices.

Application:

For protection of power supply systems.

For the protection of low voltage distribution systems against transient overvoltage caused by indirect lightning stroke and switching operations.

For using in the lightning protection zones concept at boundary 2-3.

Applied to power supply protection of equipment system in areas with high lightning risk.

Installation:

Suitable as the final stage of protection in panels with Type 2 protection devices installed upstream.

These SPDs should be installed as close as possible to the equipment being protected.

Installed at a minimum conductor length of 10 meters (30 feet) from the electrical service panel to the point of utilization, for example cord connected, direct plug-in, receptacle type SPDs installed at the utilization equipment being protected. The distance (10 meters) is exclusive of the conductors provided with or used to attach SPDs.

 