Product characteristics:
Specification | BRCI-35 | BRCI-63 | |
Description | Coordination inductor | Coordination inductor | |
Max. continuous operating voltage | Uc | 500V ac | 500V ac |
Max. line current | IL | 35A | 63A |
Line inductance | 15μH | 15μH | |
Wiring | 1 piece in series on each active line | 1 piece in series on each active line | |
Dimmension WxLxH | 36*90*65mm | 36*90*65mm | |
Connection | 6~35mm2 | 6~35mm2 | |
Mounting on | 35mm Din Rail | 35mm Din Rail | |
Operating temperature range | Tu | -40℃-80℃ | -40℃-80℃ |
Enclosure material | Thermoplastic UL-94V0 | Thermoplastic UL-94V0 | |
Degree of protection | IP20 | IP20 | |
Order Code | B6320 | B6321 |
Features:
Coordination inductors for surge protectors
These coordination inductors are specially designed to control the implementation of the primary and secondary levels of SPD surge protectors.
They are necessary where the coordination cannot be accomplished using the ‘natural’ inductance of the active conductors (in particular in a small volume, where the length of line wire between primary SPD and secondary SPD is lower than 10m).
DIN rail compatible
Connected in series on the line to be protected and depend on the maximum line current.
Further information or a personal consultation? Our products and know-how are there to provide solutions.