Product characteristics:
Specification | BR30-10DP 2P | BR75-10DP 2P | BR150-10DP 2P | BR275-10DP 2P | |
SPD classification according to EN61643-11 | Type 3 | Type 3 | Type 3 | Type 3 | |
SPD classification according to IEC61643-11 | Class III | Class III | Class III | Class III | |
Nominal a.c. voltage | Un | 24V | 60V | 120V | 230V |
Max. continuous operating a.c. voltage | Uc | 30V | 75V | 150V | 275V |
Max. continuous operating d.c. voltage | Uc | 38V | 100V | 190V | 300V |
Norminal discharge current (8/20μs) | In | 5kA | 5kA | 5kA | 5kA |
Combined impulse | Uoc | 10kV | 10kV | 10kV | 10kV |
Voltage protection level | Up | ≤200V | ≤500V | ≤700V | ≤1100V |
Response time | tA | ≤25ns | ≤25ns | ≤25ns | ≤25ns |
Operating temperature range | Tu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ |
Operating state / fault indication | green / red | green / red | green / red | green / red | |
Cross-section area (Min.) | 2.5mm² | 2.5mm² | 2.5mm² | 2.5mm² | |
Cross-section area (Max.) | 16mm² | 16mm² | 16mm² | 16mm² | |
For mounting on | 35mm Din rail | 35mm Din rail | 35mm Din rail | 35mm Din rail | |
Enclosure material | Thermoplastic UL94-V0 | ||||
Degree of protection | IP20 | IP20 | IP20 | IP20 | |
Order code | B18237 | B18235 | B18359 | B18231 | |
Order code (with remote signal) | B18238 | B18236 | B18234 | B18232 |
Features:
Product Type: Single phase 10kA 2P Power Surge Protector.
Module design, convenient installation.
Smallness leak current, response quickly, less residual voltage.
Nominal Discharge Current (8/20us): 5kA.
Maximum Discharge Current (8/20us): 10kA.
Signal indication device, green (normal), red (abnormal).
Protection Mode: 2P.
New technology, highly energy.
Production Standard: IEC61643-11.
Application:
Used for electrical networks, electrical installations, and electronic equipment.
Installed in to each electrical switch boards and prevents the spread of surges in the electric systems, protecting the loads.
It can discharge the surge current from the effect of lightning spreading from earth conductor to the network conductors.