Product characteristics:
Specification | BR-25GRS 150 3+1 | BR-25GRS 275 3+1 | BR-25GRS 320 3+1 | |
SPD classification according to EN61643-11 | Type 1 + Type 2 | Type 1 + Type 2 | Type 1 + Type 2 | |
SPD classification according to IEC61643-11 | Class I + Class II | Class I + Class II | Class I + Class II | |
Nominal operating voltage | Un | 120V/240V(50/60Hz) | 230V/400V(50/60Hz) | 250V/440V(50/60Hz) |
Max. continuous operating a.c. voltage | Uc (L-N/N-PE) | 150V/255V(50/60Hz) | 275V/255V(50/60Hz) | 320V/255V(50/60Hz) |
Lightning impulse current (10/350μs) | Iimp (L-N/N-PE) | 25kA/100kA | 25kA/100kA | 25kA/100kA |
Nominal discharge current (8/20μs) | In (L-N/N-PE) | 25kA/100kA | 25kA/100kA | 25kA/100kA |
Max. discharge current (8/20μs) | Imax (L-N/N-PE) | 50kA/160kA | 50kA/160kA | 50kA/160kA |
Quantity of electric charge (L-N, N-PE) | Q | 12.5As, 50As | 12.5As, 50As | 12.5As, 50As |
Specific energy (L-N, N-PE) | W/R | 156kJ/Ω, 2500kJ/Ω | 156kJ/Ω, 2500kJ/Ω | 156kJ/Ω, 2500kJ/Ω |
Voltage protection level | Up (L-N/N-PE) | ≤2.3kV/≤1.5kV | ≤2.3kV/≤1.5kV | ≤2.3kV/≤1.5kV |
Short-circuit current rating a.c. | Isccr (L-N/N-PE) | 25kA rms/100A rms | 25kA rms/100A rms | 25kA rms/100A rms |
Max. backup fuse | 250A gG | 250A gG | 250A gG | |
Temporary overvoltage TOV-withstand | UT (L-N) | 250V/120min. | 440V/120min. | 550V/120min. |
Temporary overvoltage TOV-withstand | UT (N-PE) | 1200V/200ms | 1200V/200ms | 1200V/200ms |
Response time | tA | ≤100ns | ≤100ns | ≤100ns |
Operating temperature range | Tu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ |
Cross-section area (Min.) | 4mm² | 4mm² | 4mm² | |
Cross-section area (Max.) | 35mm² | 35mm² | 35mm² | |
For mounting on | 35mm Din rail | |||
Enclosure material | Thermoplastic UL94-V0 | |||
Degree of protection | IP20 | IP20 | IP20 | |
Order Code | B7058 | B7071 | B7084 | |
Order Code (With remote signaling) | B7059 | B7072 | B7085 |
Features:
Type: T1+T2 Surge protector
Working voltage: 240V/400V.
Response time: ≤100ns
Normal discharge current (8/20us) In: 25kA / 100kA.
Maximum discharge current: 50kA/160kA
Labeled connections.
Maximum operating voltage: 150V/275V/320V
Composite type: 3P+NPE.
Temperature range: -40℃—80℃
Installation: standard rail 35mm.
Designed to protect low-voltage electrical installations from electrical surges caused by switching action, lightning strikes and electromagnetic pulses.
According to IEC61643-11.
Thermal disconnect device.
Screw terminal connection.
Application:
Protects electrical installations against direct lightning strokes, and discharge the back-current from lightning spreading from the earth conductor to the network conductors.
The device is designed to be used between Zone O and Zone 1 (according to IEC 62305-4 definition of Lightning Protection area).
It is installed in the power grid inlet of the 240V/400V low-voltage power supply system or in the general distribution cabinet.
Can be used to protect three-phase power system.
Matters Need Attention when install SPD:
Determine the discharge current path.
Mark the wires that produce an additional voltage drop on the device terminal.
Mark the PE conductor of each device to avoid unnecessary induction loops.
An equipotential connection is established between the device and SPD.
During installation, connect the device according to the installation diagram, where L is the phase line, N is the neutral line, and PE is the ground line. Do not misconnect the device.